Cable U/UTP LSHF cat.6 BKT 405 wire blue Dca -s2,d2,a1
Specifications
Application
- Primary (Campus), Secondary (Riser), Tertiary (Horizontal)
- IEEE 802.3: 10BASE-T; 100BASE-T, 1000BASE-T, 2.5GBASE-T, 5GBASE-T
- IEEE 802.5: 16MB, ISDN, TPDDI, ATM
- Power over Ethernet (PoE / PoE+ / PoE++)
Standards
- EN 50173-1
- EN 50288-6-1
- EN 50399
- EN 50575
- ISO/IEC 11801-1
- IEC 61156-5
- ANSI/TIA-568.2
- IEEE 802.3af/at/bt
Flame Resistance
- LSHF (LSOH, FRNC): IEC 60332-1, IEC 61034, IEC 60754-2
- CPR: ClassDca -s2,d2,a1 – EN 50399, EN 50575
Construction
- Conductor: Bare copper wire Ø 0,54mm (AWG23)
- Insulation: Polyethylene Ø 0,95mm
- Twisting: 2 cores to the pair
- Cable lay up: 4 pairs to the core, non metallic cross separator (spline)
- Sheath: LSHF (LSOH, FRNC) blue RAL 5012
Mechanical Properties ( At 20°C)
- Bending radius:
- installation: 4 x D
- installed: 8 x D
- Temperature range:
- during operation: -20°C to +60°C
- during installation: 0°C to +50°C
Electrical Properties
- DC Loop Resistance ≤ 176 Ω/km
- Resistance unbalance ≤ 2 %
- Insulation resistance: [500 V] / ≥ 5000 MΩkm
- Mutual capacitance: [800 Hz] / nom. 48 nF/km
- Capacitance unbalance: [pair/ground] / ≤ 1500 pF/km
- Characteristic impedance: [100 MHz] / 100 ± 5 Ω
- Nominal Velocity of Propagation: NVP / 67 %
- Propagation Delay: ≤ 535 ns/100m
- Delay Skew: ≤ 20 ns/100m
- Test Voltage: [DC, 1min] 1000 V
- Coupling attenuation: ≥ 40 dB
- Separation clasification according to EN 50174-2 „b”
Useful Properties
- Fire Load: 316 MJ/km – 0.087 kWh/m
- Tensile force: 100N
Technical Data
- Cable Type: J-2YH 4x2x0.54
- Declaration of Performance (DoP): 11213344
- Outder diameter (mm): 5.3
- Weight (kg/km): 36